Building Intelligence

Wireless Precision Data Acquisition Node - Performance/Functional Specifications

Overview Performance Mounting Connectivity


Performance/Functional Specifications

Communication Electrical/Performance
Wired CAN mode per repeater
Max Distance 1000m 22 AWG control wire
Max Nodes 128 nodes
CAN Interface CAN 2.0B (ISO 11898)
CAN Speed 10kbps
Input Power 3.6VDC to 12VDC
Wireless
Specification IEEE 802.15.4
Max Distance from coordinator

30m (with included antenna, extended ranges up to 350m available with optional external antennas) 

Max Nodes per 128 (depends on application density and acquisition speed)
Battery Life 15 years (one sample per hour)
Environmental  
Operating Temperature 0° to 40°C / 32° to 104°F
Storage Temperature -25° to 70°C / -13° to 158°F
Humidity 5% to 90% RH non-condensing
Electrostatic Discharge (ESD) 8kVdc air, 4 kVDC contact

 

Mechanical  
Standard Enclosure  
Dimensions 147mm (L) x 89 mm (W) x 24mm(H)
Weight 200g
Watertight Enclosur  
Dimensions 118mm (L) x 90 mm (W) x 60mm(H)
Weight 200g
Rating IP66 and NEMA
Junction Box Mount  
Dimensions 90 mm (L) x 91 mm (W)
Connectorization  
CAN (in/out) Single RJ45
External Sensors Terminal Block/Pressure Tubing
Interface

Red/Green LEDs

Reset/Config Button

 

Measurement Electrical/Performance  
Relative Humidity  
Sensor Humeril HTM2500
Range 0-100% RH
Resolution ±0.1%
Accuracy ±2%
Temperature  
Sensor Analog Devices ADR421
Range -40°C to +70°C
Resolution 0.1°C
Accuracy ±1°C
Differential Pressure  
Sensor Freescale Dual Port MPXV7002DP
Range -2kPa to +2kPa
Resolution 0.1Pa
Accuracy ±1Pa
Resistance  
Range 100Ω to 1KΩ
Resolution 10Ω
Accuracy ±5%
   
Range 1KΩ to 10KΩ
Resolution 100Ω
Accuracy ±5%
   
Range 10KΩ to 100KΩ
Resolution 1KΩ
Accuracy ±5%
   
Range 100KΩ to 1MΩ
Resolution 10KΩ
Accuracy ±5%
   
Range 1MΩ to 10MΩ
Resolution 100KΩ
Accuracy ±5%
   
Range 10MΩ to 100MΩ
Resolution 1MΩ
Accuracy ±10
Expansion Connectors  
Digital 3.3V, Timer, Interrupt, SPI bus, PIC control, Chip Selects, A/D channel
Analog -3V, 6V, 5V, Vref, 2 A/D channels, access to J5 terminal connecto
Regulatory Requirements (pending)  
EMC Radiated and Conducted Emissions FCC Part 15 Class B Industry Canada ICES 003
Safety Requirements cULus and CE