Building Intelligence

Wireless Precision Data Acquisition Node - Sensor Connectivity

Overview Performance Mounting Connectivity

Sensor Connectivity

Pin Symbol Function
1 R1+ Resistance +
2 R1- Resistance -
3 R2+ Resistance +
4 R2- Resistance -
5 V1 Voltage
6 V2 Voltage
7 GND Ground
8 5V Power

 

 

 

Resistance/Moisture Content

  • • Channel 1: Connect moisture pins or Moisture Detection Tape to R1+ and R1-
  • • Channel 2: Connect moisture pins or Moisture Detection Tape to R2+ and R2-

 

Temperature

  • • For built in temperature reading no connectivity required.
  • • External thermistor. Connect 104JT thermistor to R1+ and R1- or R2+ and R2-

 

Relative Humidity

HTM2500 WiDAQ Function
Brown Pin 7 GND
White Pin 8 +5V
Yellow Pin 5 or 6 (V1 or V2) RH
Green

Pin 1 or 3 (R1+ or R2+)

R1- and R2- to GND

°C
Black   Shield

Differential Pressure

  • • Mate extension tubes to the tubes provided.
  • • Route tubes to locations where the differential pressure measurement is required.

 

Wired CAN Connectivity

 


 

  • • Connect gateway computer to the RJ45 connector on the WiDAQ.
  • • At least one wired WiDAQ is required per system. Depending on the topology of the sensors, quantity and placement will need to be specified.